Cable Manager capacity table
The following capacity table applies toSimon horizontal cable manager, vertical cable Manager and rack To assist in capacity planning。
The values reflect the calculated capacity and the actual capacity at 100% full load. If cables are properly arranged, the actual capacity will be affected。
总 面积 (sq. in.) | 有效 面积 (sq. in.) | Cable Diameter (mm) | ||||||||||||
0.13 | 0.15 | 0.17 | 0.19 | 0.21 | 0.23 | 0.25 | 0.27 | 0.29 | 0.31 | 0.33 | 0.35 | |||
(3.30) | (3.81) | (4.32) | (4.83) | (5.33) | (5.84) | (6.35) | (6.86) | (7.37) | (7.87) | (8.38) | (8.89) | |||
Horizontal cable manager | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
HCM(E)-4-1U | 3.04 | 1.21 | 71 | 53 | 42 | 33 | 27 | 22 | 19 | 16 | 14 | 12 | 11 | 9 |
HCM(E)-4-2U(-D)1 | 9.89 | 3.96 | 234 | 175 | 136 | 109 | 89 | 74 | 63 | 54 | 47 | 41 | 36 | 32 |
HCM(E)-4-4U | 23.59 | 9.44 | 558 | 419 | 326 | 261 | 214 | 178 | 151 | 129 | 112 | 98 | 86 | 77 |
HCM(E)-6-1U | 4.29 | 1.71 | 101 | 76 | 59 | 47 | 38 | 32 | 27 | 23 | 20 | 17 | 15 | 13 |
HCM(E)-6-2U(-D)1 | 14.64 | 5.85 | 346 | 260 | 202 | 162 | 132 | 110 | 93 | 80 | 69 | 60 | 53 | 47 |
HCM(E)-6-4U | 35.34 | 14.13 | 836 | 628 | 489 | 391 | 320 | 267 | 226 | 193 | 168 | 147 | 129 | 115 |
PH-3 | 6.50 | 2.60 | 153 | 115 | 89 | 72 | 58 | 49 | 41 | 35 | 30 | 27 | 23 | 21 |
RS(3)-RWM-1 | 3.50 | 1.40 | 82 | 62 | 48 | 38 | 31 | 26 | 22 | 19 | 16 | 14 | 12 | 11 |
RS(3)-RWM-2 | 9.01 | 3.60 | 213 | 160 | 124 | 99 | 81 | 68 | 57 | 49 | 42 | 37 | 33 | 29 |
RS(3)-RWM-2DS1 | 9.01 | 3.60 | 213 | 160 | 124 | 99 | 81 | 68 | 57 | 49 | 42 | 37 | 33 | 29 |
RS(3)-RWM-4 | 23.44 | 9.38 | 554 | 416 | 324 | 259 | 212 | 177 | 150 | 128 | 111 | 97 | 86 | 76 |
RS(3)-RWM6-2 | 15.13 | 6.05 | 357 | 268 | 209 | 167 | 137 | 114 | 96 | 82 | 71 | 62 | 55 | 49 |
RS(3)-RWM6-4 | 33.00 | 13.20 | 781 | 586 | 456 | 365 | 299 | 249 | 211 | 181 | 156 | 137 | 121 | 107 |
RWM-1 | 2.89 | 1.16 | 68 | 51 | 40 | 32 | 26 | 21 | 18 | 15 | 13 | 12 | 10 | 9 |
RWM-1DS1 | 2.89 | 1.16 | 68 | 51 | 40 | 32 | 26 | 21 | 18 | 15 | 13 | 12 | 10 | 9 |
S110-RWM-(XX) | 3.20 | 1.28 | 75 | 56 | 44 | 35 | 29 | 24 | 20 | 17 | 15 | 13 | 11 | 10 |
S110-RWM2-(XX) | 8.40 | 3.36 | 198 | 149 | 116 | 93 | 76 | 63 | 53 | 46 | 39 | 34 | 30 | 27 |
WM-143-5 | 2.80 | 1.12 | 66 | 49 | 38 | 31 | 25 | 21 | 17 | 15 | 13 | 11 | 10 | 9 |
WM-144-5 | 5.72 | 2.29 | 135 | 101 | 79 | 63 | 51 | 43 | 36 | 31 | 27 | 23 | 21 | 18 |
WM-145-5 | 10.00 | 4.00 | 236 | 177 | 138 | 110 | 90 | 75 | 64 | 54 | 47 | 41 | 36 | 32 |
Rack and vertical cable manager | ||||||||||||||
RS-07(-S) Channel | 18.00 | 7.20 | 426 | 320 | 249 | 199 | 163 | 136 | 115 | 98 | 85 | 74 | 66 | 58 |
RS-07(-S) Front Managers | 6.50 | 2.60 | 153 | 115 | 89 | 72 | 58 | 49 | 41 | 35 | 30 | 27 | 23 | 21 |
RS-07E Channel | 43.50 | 17.40 | 1029 | 773 | 602 | 481 | 394 | 328 | 278 | 238 | 206 | 181 | 159 | 142 |
RS-07E Front Managers | 6.50 | 2.60 | 153 | 115 | 89 | 72 | 58 | 49 | 41 | 35 | 30 | 27 | 23 | 21 |
RS3-07(-S) Channel | 27.60 | 11.04 | 653 | 490 | 382 | 305 | 250 | 208 | 176 | 151 | 131 | 114 | 101 | 90 |
RS3-07(-S) Front Managers | 14.31 | 5.72 | 338 | 254 | 198 | 158 | 129 | 108 | 91 | 78 | 68 | 59 | 52 | 46 |
RS-CNL | 44.75 | 17.90 | 1059 | 795 | 619 | 495 | 405 | 338 | 286 | 245 | 212 | 186 | 164 | 146 |
RS-CNL3 | 26.75 | 10.70 | 633 | 475 | 370 | 296 | 242 | 202 | 171 | 146 | 127 | 111 | 98 | 87 |
VCM-6 | 64.83 | 25.93 | 1534 | 1152 | 897 | 718 | 588 | 490 | 414 | 355 | 308 | 269 | 238 | 211 |
VCM-6 Base2 | 48.24 | 38.59 | 2283 | 1715 | 1335 | 1069 | 875 | 729 | 617 | 529 | 458 | 401 | 354 | 315 |
VCM-6D3 | 90.83 | 36.33 | 2149 | 1614 | 1257 | 1006 | 823 | 686 | 581 | 498 | 432 | 378 | 333 | 296 |
VCM-6D Base2 | 61.17 | 48.93 | 2895 | 2174 | 1693 | 1355 | 1109 | 924 | 782 | 671 | 581 | 509 | 449 | 399 |
VCM-10 | 111.55 | 44.62 | 2640 | 1983 | 1543 | 1235 | 1011 | 843 | 713 | 612 | 530 | 464 | 409 | 364 |
VCM-10 Base2 | 88.75 | 71.00 | 4201 | 3155 | 2456 | 1966 | 1610 | 1342 | 1136 | 973 | 844 | 738 | 651 | 579 |
VCM-10D3 | 160.73 | 64.29 | 3804 | 2857 | 2224 | 1780 | 1457 | 1215 | 1028 | 881 | 764 | 669 | 590 | 524 |
VCM-10D Base2 | 118.65 | 94.92 | 5616 | 4218 | 3284 | 2629 | 2152 | 1794 | 1518 | 1302 | 1128 | 987 | 871 | 774 |
VCM-12 | 134.91 | 53.96 | 3193 | 2398 | 1867 | 1494 | 1223 | 1020 | 863 | 740 | 641 | 561 | 495 | 440 |
VCM-12 Base2 | 109.01 | 87.21 | 5160 | 3875 | 3017 | 2415 | 1977 | 1648 | 1395 | 1196 | 1036 | 907 | 800 | 711 |
VCM-12D3 | 195.68 | 78.27 | 4631 | 3478 | 2708 | 2168 | 1774 | 1479 | 1252 | 1073 | 930 | 814 | 718 | 638 |
VCM-12D Base2 | 147.39 | 117.91 | 6976 | 5240 | 4079 | 3266 | 2673 | 2228 | 1886 | 1617 | 1401 | 1226 | 1082 | 962 |
VCM-16 | 181.63 | 72.65 | 4298 | 3228 | 2513 | 2012 | 1647 | 1373 | 1162 | 996 | 863 | 755 | 667 | 593 |
VCM-16 Base2 | 149.52 | 119.62 | 7077 | 5316 | 4138 | 3313 | 2712 | 2261 | 1913 | 1640 | 1422 | 1244 | 1098 | 976 |
VCM-16D3 | 265.57 | 106.23 | 6285 | 4721 | 3675 | 2942 | 2408 | 2008 | 1699 | 1457 | 1263 | 1105 | 975 | 867 |
VCM-16D Base2 | 204.87 | 163.89 | 9697 | 7284 | 5671 | 4539 | 3716 | 3098 | 2622 | 2248 | 1948 | 1705 | 1504 | 1337 |
VPC(A)-12 Front Channel | 61.88 | 24.75 | 1464 | 1100 | 856 | 685 | 561 | 467 | 396 | 339 | 294 | 257 | 227 | 202 |
VPC(A)-12 Rear Channel | 89.50 | 35.80 | 2118 | 1591 | 1238 | 991 | 811 | 676 | 572 | 491 | 425 | 372 | 328 | 292 |
VPC(A)-6 Front Channel | 28.88 | 11.55 | 683 | 513 | 399 | 319 | 261 | 218 | 184 | 158 | 137 | 120 | 106 | 94 |
VPC(A)-6 Rear Channel | 44.75 | 17.90 | 1059 | 795 | 619 | 495 | 405 | 338 | 286 | 245 | 212 | 186 | 164 | 146 |
Cabinet cable manager | ||||||||||||||
Cabinet Lid Small Cable Access Panel2 | 19.25 | 15.40 | 911 | 684 | 532 | 426 | 349 | 291 | 246 | 211 | 183 | 160 | 141 | 125 |
Cabinet Lid Large Cable Access Panel2 | 87.50 | 70.00 | 4142 | 3111 | 2422 | 1939 | 1587 | 1323 | 1120 | 960 | 832 | 728 | 642 | 571 |
VP-VPC4 | 27.20 | 10.88 | 643 | 483 | 376 | 301 | 246 | 205 | 174 | 149 | 129 | 113 | 99 | 88 |
VP-VPC6-1-(XX)4 | 40.80 | 16.32 | 965 | 725 | 564 | 452 | 370 | 308 | 261 | 223 | 194 | 169 | 149 | 133 |
V8A-VPC4-1-(XX) | 18.06 | 7.23 | 427 | 321 | 250 | 200 | 163 | 136 | 115 | 99 | 85 | 75 | 66 | 58 |
V8A-VPC6-1-(XX) | 26.56 | 10.63 | 628 | 472 | 367 | 294 | 240 | 200 | 170 | 145 | 126 | 110 | 97 | 86 |
V8A-VPC145-1-(XX) | 10.79 | 4.32 | 255 | 191 | 149 | 119 | 97 | 81 | 69 | 59 | 51 | 44 | 39 | 35 |
VP-EVPC6-1-(XX) | 21.00 | 8.40 | 497 | 373 | 290 | 232 | 190 | 158 | 134 | 115 | 99 | 87 | 77 | 68 |
Other cable managers | ||||||||||||||
6" Hook & Loop Cable Manager | 2.29 | 0.92 | 54 | 40 | 31 | 25 | 20 | 17 | 14 | 12 | 10 | 9 | 8 | 7 |
12" Hook & Loop Cable Manager | 9.17 | 3.67 | 217 | 163 | 126 | 101 | 83 | 69 | 58 | 50 | 43 | 38 | 33 | 29 |
18" Hook & Loop Cable Manager | 20.64 | 8.25 | 488 | 366 | 285 | 228 | 187 | 156 | 132 | 113 | 98 | 85 | 75 | 67 |
RS-CH | 6.50 | 2.60 | 153 | 115 | 89 | 72 | 58 | 49 | 41 | 35 | 30 | 27 | 23 | 21 |
RS-VCM/VP-VCM | 20.64 | 8.25 | 488 | 366 | 285 | 228 | 187 | 156 | 132 | 113 | 98 | 85 | 75 | 67 |
S110A1RMS-(XX) | 3.20 | 1.28 | 75 | 56 | 44 | 35 | 29 | 24 | 20 | 17 | 15 | 13 | 11 | 10 |
S110A2RMS-(XX) | 8.40 | 3.36 | 198 | 149 | 116 | 93 | 76 | 63 | 53 | 46 | 39 | 34 | 30 | 27 |
S110B1RMS-(XX) | 3.20 | 1.28 | 75 | 56 | 44 | 35 | 29 | 24 | 20 | 17 | 15 | 13 | 11 | 10 |
S110B2RMS-(XX) | 8.40 | 3.36 | 198 | 149 | 116 | 93 | 76 | 63 | 53 | 46 | 39 | 34 | 30 | 27 |
S143/VP-143 | 2.80 | 1.12 | 66 | 49 | 38 | 31 | 25 | 21 | 17 | 15 | 13 | 11 | 10 | 9 |
S144 | 5.72 | 2.29 | 135 | 101 | 79 | 63 | 51 | 43 | 36 | 31 | 27 | 23 | 21 | 18 |
S145/VP-145 | 10.00 | 4.00 | 236 | 177 | 138 | 110 | 90 | 75 | 64 | 54 | 47 | 41 | 36 | 32 |
S146 | 18.24 | 7.30 | 431 | 324 | 252 | 202 | 165 | 137 | 116 | 100 | 86 | 75 | 66 | 59 |
S147 | 29.64 | 11.86 | 701 | 526 | 410 | 328 | 268 | 224 | 189 | 162 | 140 | 123 | 108 | 96 |
注:
- The cable capacity of the manager reflects the calculated 40% fill rate, which is intended to reflect the 100% fill condition due to cable in/out during actual use。
- If redundant storage is used, this capacity should be further reduced by 50%, corresponding to the case where a single cable is coiled twice in the manager。
- It reflects the cable capacity on one side
- The cable capacity of the opening that only allows cables to pass through reflects the calculated value of 80% filling rate, which is intended to reflect the 100% filling state when cables are properly arranged
- The capacity of the two-sided manager applies to the entire manager - the value can be 40%, 50%, or 60% when calculating unilateral capacity depending on the location of the internal partition
- You can increase the cable capacity by 30% by installing bolts to the rear of the VPC backplane